TH9310 Series AC/DC Withstanding Voltage/Insulation Resistance Tester
-
Quality Control: Hipot testing is an integral part of quality control processes in electrical manufacturing. It helps ensure that electrical components, cables, and devices meet the required insulation strength and safety standards before they are released to the market.
Features
TH9310 series: AC:5kV/10mA; DC:6kV/5mA AC/ DC withstanding voltage/insulation resistance tester
TH9320 series: AC:5kV/20mA; DC6kV/10mA AC/ DC withstanding voltage/insulation resistance tester
TH9310/20:AC/ DC withstanding voltage/insulation resistance tester
TH9310B: AC withstanding voltage tester
480×272 dot-matrix, TFT-LCD display
Rapidly discharging and arc detection
Randomly set voltage rising time and testing time in 999.9 seconds; Freely set waiting time for insulation resistance
Hold 5 testing steps; 4 testing modes selectable
Brand new operation interface and concise interface operation design
Lock keyboard
PLC interface
Brief Introduction
TH9310/20 series withstanding voltage/insulation resistance tester is an economical and intelligent safety tester with the characteristics of small size, light weight,pleasing appearance and easy operation. TH9310/20 series can be widely used in the safety tests of household appliances, transformer, electrical equipments and components
Specifications
Model | TH9310/20 | TH9310B | ||
Withstanding Voltage Test | ||||
Output Voltage | AC | 0.05 —5.00kV(2% reading+5digits), (50Hz,60Hz optional) | ||
DC | 0.05 —6.00kV(2% reading+5digits) | ------ | ||
Voltage Adjustment Rate | ≤ (1% - 5V)(rated power) | |||
Current TestRange | AC | TH9310:0.000mA 10.00mA(2% reading+2digits) TH9320:0.000mA 20.00mA(2% reading+2digits) |
||
DC | TH9310:0uA 5.00mA(2% reading+2digits) TH9320:0uA 10.00mA(2% reading+2digits) |
------ | ||
Discharge Function | Discharge after test ends(DCW) | |||
Insulation Resistance Test | ||||
Output Voltage | 0.10kV 1.00kV(2%reading+2V) | ------ | ||
Resistance Test Range | 1M 9999M | ------ | ||
Resistance Test Accuracy | 500V-1000V | 1M 1000M(5%reading+2digits) 1000M9999M(10%reading+2digits) |
------ | |
100V-500V | 1M 1000M(10%reading+2digits) | ------ | ||
Discharge Function | Discharge after test ends | ------ | ||
Arc Detection | ||||
Measurement Range | AC | 1 9 levels (factory default 5) 20mA,18mA, 16mA, 14mA, 12mA, 10mA, 7.7mA, 5.5mA, 2.8mA respectively) |
||
DC | 1 9 levels | ------ | ||
General Specification | ||||
Memory | 5 groups | |||
Voltage Rising Time | 0.1s 999.9s | |||
Test Time Setting(AC/DC) | 0.2s 999.9s | |||
Waiting Time(IR) | 0.2s 999.9s | ------ | ||
Time Accuracy | ±(1%+0.1s) | |||
Dimension(W×H×D) | 280mm×89mm×428mm/10kg | |||
Interface | ||||
Standard | HANDLER, RS232, USBDRV(PC interface), USBHOST(USB port) |
Accessary
Standard | ||||||
Accessories name | Model | |||||
High Voltage Test Cable (Red) | TH90003R | |||||
High Voltage Test Cable | TH90003C |
Optional | ||||||
Accessories name | Model |